Fireglide Temperature-P

The Fireglide Temperature-P carries a CE mark and is approved for applications where thermal insulation is required. The doors are rated for up to 90 minutes of protection according to fire resistance class EI2 and up to 60 minutes according to fire resistance class EI1. If it is 1000°C on the fire side of the door, it will not get hotter than 140°C on the other side of the door. This makes the door very suitable for applications along an evacuation route. 

Fire, smoke and intensive use
In addition to being fire-resistant, the Fireglide Temperature is also available in a smoke-resistant version. This protects at normal ambient temperatures (Sa) or up to 200 degrees (S200). One or two escape doors can be incorporated in the door surface.

All door types are suitable for high intensity of use, as they are also tested according to the EN 12605 standard. The heaviest door type has a C3 rating and can open and close 50,000 times without compromising protection. The lighter versions have a C4 class 100,000 cycles) or even a C5 class (200,000 cycles), depending on the total surface area. This makes them ideally suited for use in industry, offices, lodging buildings and parking garages, among others.

Fireglide Temperature P EO6A9564

Why Fireglide Temperature-P (EI)?

30 minutes fire resistant

  • Fire resistance: EI230
  • Maximum clear opening: 16.000 x 5.500 mm (w x h)
  • Maximum surface area: 50 m2

60 minutes fire resistant

  • Fire resistance: EI160
  • Maximum clear opening: 8.000 x 5.000 mm (w x h)
  • Maximum surface area: 40 m2

90 minutes fire resistant

  • Fire resistance: EI290
  • Maximum clear opening: 8.000 x 5.000 mm (w x h)
  • Maximum surface area: 40 m2

Smoke resistant

  • Smoke resistance: S200
  • Maximum clear opening: 6,940 x 4,920 mm (w x h)
  • Maximum surface area: 34.14 m2
  • Smoke resistant to 200°C.