Technical information on Firelock fire-resisting roller shutters
Door leaf
BD120
The armour is made from flat, double-walled galvanised steel sections, material thickness 2 x 1 mm, provided with a mineral wool filling.
All the extremities of the sections are locked to each other to prevent horizontal movement between them.
B120E
The armour is made from flat, double-walled galvanised steel sections, material thickness 2 x 0.8 mm, provided with a mineral wool filling.
All the extremities of the sections are locked to each other to prevent horizontal movement between them.
Suitable for application in industrial, office, and accommodation buildings, shipping etc.
Fire resistance:
BD120
- double-sided 120 min. up to clear width of 6000 mm x 6000 mm (wxh), max. opening area 24 m2
- double-sided 90 min. up to clear width of 10000 mm x 8000 mm (wxh), max. opening area 35 m2
- double-sided 60 min. up to clear width of 11750 mm x 7545 mm (wxh).
Attestations of equivalence applicable.
B120E
- double-sided 120 min. up to clear width of 3613 mm x 3036 mm (wxh),
- double-sided 60 min. up to clear width of 4000 mm x 4250 mm (wxh).
Attestations of equivalence applicable.
Test results:
- tested at TNO according to NEN 6069 and the Buildings Decree, KOMO affidavit also present.
Section thickness:
- 22 mm
Working height:
- approx 100 mm
Motor and controls
Operation of fire-resisting roller shutter
The shutter is driven by a 380 volt three-phase motor with a built-in braking system, designed specially for the fire-resisting roller door The control system is mounted inside a separate plastic casing attached to the motor.
In case of fire, the fire alarm system gives a command to the motor whereafter the fire‑resisting roller door is lowered at a controlled descent speed. In the case of a fire alarm or power failure, the electromagnetic brake is released, whereafter the fire-resisting roller door is lowered at a controlled descent speed.
The motor is provided as standard with emergency manual control by means of a flywheel. Using this control the roller shutter cannot be used as an emergency exit. An emergency supply battery is optional.
Smart Control box
All roller shutters and roller gates (except 220 V tubular motors combined with single switch) are provided as standard with the comprehensive Smart Control box. A control box with traffic regulation is optional.
The Smart Control box is provided with four signal lamps to indicate the following:
- indication of a maintenance check based on time and number of movements;
- power supply present;
- faults
(To allow our fitters to read out faults a memory function is provided). - check that the motor rotates the correct way.
At the same time, the Smart Control box checks the roller shutter for:
- running time protection;
- continuous motor current; on overload, the motor is switched off;
- a delay time of one second to protect the motor when changing direction up-down and vice versa.
By using special software the standard control may easily be expanded with various functions.
Closing system
By means of signalling a closing command will ensure that the fire-resisting roller door closes automatically.
Control
Control is done using a push-button switch up-stop-down next to the barrier.
The closing operation is implemented as a ‘dead man's switch’ as standard, whereby a down command must be given permanently.